GE Zenith
- ZTGSE
Series Transfer Switches -
Service Entrance, Enclosed Only.
Zenith is of the world leaders in emergency and
standby power transfer solutions, Zenith keeps your
power on. Zenith is committed to providing a full
range of quality-driven products, backed by
nationwide 24-hour service and support.
The switches in this group are designed for specific critical applications.
They are utilized in industrial standard applications requiring dependability
and ease of operation. These switches
combine reliability, flexibility and ease of use in a rugged industrial package.
All these switches
work together with any remote-start generator that use two-wire control,
allowing the standby power system to be fully automatic.
Designed for specific applications, this Series builds on ZTS technology while
providing a pre-engineered project solution.
The ZTS Series is the building block of our transfer switch
product line including all the switches shown on this page. This ruggedly built
power contactor family of switches has been specifically designed for transfer
switch duty with dependability, versatility and user friendliness of prime
concern. These special switches are available in NEMA enclosures to the
customer’s specifications
.
The Model SE expands the time-tested Series ZTG
platform to serve more applications than ever before.
While providing the functionality of an automatic
transfer switch the ZTGSE integrates the utility main disconnect, optional
transient voltage surge suppression and power monitoring into one simple
coordinated package.
The ZTGSE provides greater protection to critical
loads against utility power outages and transient voltage disturbances. This
delivers more piece of mind to facility managers and business owners in a wide
range of industries such as water/wastewater reclamation, retail, agricultural,
light manufacturing, wireless communications and other service businesses.
ZTGSE switches are equipped with GE’s next-generation
MX150 microprocessor panel, which controls the operation and indicates the
status of the transfer switch’s position and available sources. As an embedded
digital controller, the MX150 offers best-in-class performance utilizing an LCD
display with statistical event recording and basic metering as standard
features.
General Information:
GE Zenith’s
ZTGSE
Series Transfer Switches
are designed for emergency, critical and life support standby and
prime power applications.
Standard models in stock, dropped shipped to your location.
FREE SHIPPING when purchased with a generator!
Sizes include 40 to 3,000 amps with 2, 3 or 4 pole
configurations.
Available 120/240 VAC, 120/208 VAC, 277/480 VAC and other
voltages up to 600 VAC. See Factory Brochure under Additional
Information.
Switch is true double throw, mechanically interlocked and
mechanically held, electrically operated utilizing a reliable,
field-proven single solenoid operator.
Switch mechanism absolutely prohibits connecting both sources
together. Cannot be over-ridden.
Available in
standard or delayed transistion configurations.
Available in NEMA Type 1 (indoor), 3R (outdoor) enclosures and
open (back-panel mounted) configurations as well as NEMA 4, 4X & 12.
Dimensions shown on ZTS Dimensions under Additional Information.
GE Zenith’s ZTGSE switches are equipped with the
MX150 control panel.
This microprocessor control includes:
Under-voltage sensing (90% pickup, 80% dropout) of Source 1
(normal).
Voltage and frequency sensing of Source 2 (emergency), (90%
voltage, 95% frequency pickup).
Time Delay
Engine Warm-up
(W)
- Transfer to Emergency (Source 2) - 0 -5 minutes, factory setting 1
second.
Time Delay
Utility Stabilization/Retransfer to Utility (Source 1)
(T)
- 0-60 minutes, factory setting 30 minutes.
Time Delay
Engine Cool Down
(U)
-
0-60 minutes, factory setting 5 minutes.
Generator exerciser timer built-in. 365 day adjustable time
setting. Factory set at 7 days. Exercises Source 2 with or without
load.
Switches feature contacts that are easily accessible for easy
inspection and preventive maintenance.
Rated for standby applications and
intended for use only in optional (non-critical) standby systems in
accordance with the National Electrical Code. NEC/NFPA 70, Article
702.
Not intended for emergency or life-support systems.
Meets NEC requirements for use as Service
Entrance Equipment.
Qualified and listed to
UL 1008, CSA 22.2 and IEC,
480 VAC 50/60 Hz for
automatic transfer equipment standards.
Fully approved for UL891, UL 1449 (with
TVSS feature
For technical data, dimensions,
features, remote controls, monitoring, warranty and other
information.
See Additional Information below.
CALL FOR PRICING: Due to the
extensive array of types, options and accessories please contact the
GeneratorJoe sales department for competitive pricing. Call GeneratorJoe at 707
539-9003 or write
sales@generatorjoe.net.